(b) Master station (CC-Link Ver.2 board) (RY) Remote device
station (RY)
The following formula indicates the time taken from the moment RY of the
master station (CC-Link Ver.2 board) turns on (off) until the remote device
station output turns on (off). ( 3)
[Formula]
[Normal value]
α
1 + (LR m) + LS (1 (2 n -1) + 1) + Remote I/O station response time
[ms] ( 4)
[Maximum value]
α
1 + (LR m) + LS (2 (2 n -1) + 1) + Remote I/O station response time
[ms] ( 4)
α
1: Request processing time of the personal computer
LR: Link refresh time
LS: Link scan time (refer to Appendix 3.1)
m: LS/LR (However, the decimal point is rounded up)
n: Expanded cyclic setting (n time setup)
Note that n=1 is used for a Ver.1 compatible slave station.
3: The above one is shown by the example of the remote device station (RY),
but it is also applicable for the remote device station (RWw).
4: When writing RY to the CC-Link Ver.2 board with the md function, it is
necessary to add the own station access processing time of the md function.