3 - 6 3 - 6
MELSEC
3 SPECIFICATIONS
3.2.2 Maximum overall cable distance (for Ver.1.00)
The relationship between the transmission speed and the maximum overall cable
distance is described below:
(1) For a system consisting of only remote I/O stations and remote
device stations
Maximum overall cable distance
Remote I/O station
or remote
device station
Master station
Remote I/O station
or remote
device station
Remote I/O station
or remote
device station
Remote I/O station
or remote
device station
2
2
1
1
1: Cable length between remote I/O stations or remote device stations.
2: Cable length between the master station and the adjacent stations.
CC-Link dedicated cable (uses terminal resistor 110
)
Transmission rate
Station-to-station cable length
Maximum overall cable distance
1
2
156 kbps
30 cm (11.81 in.) or more
1 m (3.28 ft.) or more
1200 m (3937.2 ft.)
625 kbps
600 m (1968.6 ft.)
2.5 Mbps
200 m (656.2 ft.)
5 Mbps
30 cm (11.81 in.) to
59 cm (23.23 in.)
3
110 m (360.9 ft.)
60 cm (23.62 in.) or more 150
m
(492.15 ft.)
10 Mbps
30 cm (11.81 in.) to
59 cm (23.23 in.)
3
50 m (164.1 ft.)
60 cm (23.62 in.) to
99 cm (38.98 in.)
3
80 m (262.5 ft.)
1 m (3.28 ft.) or more
100 m (328.1 ft.)
CC-Link dedicated high performance cable (uses terminal resistor 130
)
Transmission rate
Station-to-station cable length
Maximum overall cable distance
1
2
156 kbps
30 cm (11.81 in.) or more
1 m (3.28 ft.) or more
1200 m (3937.2 ft.)
625 kbps
900 m (2952.9 ft.)
2.5 Mbps
400 m (1312.4 ft.)
5 Mbps
160 m (524.96 ft.)
10 Mbps
Number of connected
stations: 1 to 32
100 m (328.1 ft.)
Number of connected
stations: 33 to 48
30 cm (11.81 in.) to
39 cm (15.35 in.)
3
80 m (262.5 ft.)
40 cm (15.75 in.) or more 100
m
(328.1 ft.)
Number of connected
stations: 49 to 64
30 cm (11.81 in.) to
39 cm (15.35 in.)
3
20 m (65.52 ft.)
40 cm (15.75 in.) to
69 cm (27.17 in.)
3
30 m (98.43 ft.)
70 cm (27.56 in.) or more 100
m
(328.1 ft.)
3: The cable length between remote I/O stations or remote device stations is within this
range and if even one location is wired, the maximum overall cable distance will be
as indicated above.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......