14 - 8 14 - 8
MELSEC
14 COMMUNICATION BETWEEN THE MASTER STATION AND
INTELLIGENT DEVICE STATION (AJ65BT-D75P2-S3)
User Program
CC-Link Ver.2 Board
1) Turns ON the initial data setting request flag
(RY79).
2) Turns ON the initial data setting request flag
(RY79) on the AJ65BT-D75P2-S3.
3) The AJ65BT-D75P2-S3 turns ON the initial data
setting complete flag (RX79).
4) Reads out the initial data setting complete flag
(RX79).
5) With the initial data setting complete flag (RX79)
ON, writes start No. to the Axis 1 positioning start
No. setting area (RWw0) and Axis 2 positioning
start No. setting area (RWw8).
6) Writes the start No. to the Axis 1 positioning start
No. setting area (RWw0) and Axis 2 positioning
start No. setting area (RWw8) of the AJ65BT-
D75P2-S3.
7) Turns OFF the initial data setting request flag
(RY79).
8) The AJ65BT-D75P2-S3 turns OFF the initial data
setting request flag (RY79).
9) The AJ65BT-D75P2-S3 turns OFF the initial data
setting complete flag (RX79), and turns ON the
remote station READY flag (RX7B).
10) Reads out the initial data setting complete flag
(RX79) and the remote station READY flag
(RX7B).
11) With the initial data setting complete flag (RX79)
OFF and the remote station READY flag (RX7B)
ON, turns ON the Axis 1 servo ON flag (RY20)
and Axis 2 servo ON flag (RY40).
12) Turns ON the Axis 1 servo ON flag (RY20) and
Axis 2 servo ON flag (RY40) of the AJ65BT-D75P2
-S3.
13) Turns ON the Axis 1 positioning start flag (RY10)
and Axis 2 positioning start flag (RY11).
14) Turns ON the Axis 1 positioning start flag (RY10)
and Axis 2 positioning start flag (RY11) on the
AJ65BT-D75P2-S3.
The AJ65BT-D75P2-S3 starts the zero point return
operation.
Parameters set in the sample program
For zero point return
Basic parameters
Extended parameters
Axis 1
Zero point return method:
5 (counting system 2 (zero-point signal is not used))
Zero point return direction: 0 (forward direction)
Zero point address: 0
Zero point return speed: 2000
Creep speed: 1000
Zero point return retry: 0 (no retry)
Zero point return dwell time: 0
Displacement setting after near-point dog: 1000
Zero point return acceleration time selection: 0
Zero point return deceleration time selection: 0
Zero point shift amount: 0
Zero point return torque limit value: 300
Speed designation during zero point shift: 0
Dwell time during zero point return retry: 0
Axis 2
Zero point return method:
5 (counting system 2 (zero-point signal is not used))
Zero point return direction: 0 (forward direction)
Zero point address: 0
Zero point return speed: 2000
Creep speed: 1000
Zero point return retry: 0 (no retry)
Zero point return dwell time: 0
Displacement setting after near-point dog: 1000
Zero point return acceleration time selection: 0
Zero point return deceleration time selection: 0
Zero point shift amount: 0
Zero point return torque limit value: 300
Speed designation during zero point shift: 0
Dwell time during zero point return retry: 0
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......