6 - 11 6 - 11
MELSEC
6 PARAMETER SETTINGS
6.5 Status Difference Between a Master Station and a Slave Station at an Error
The status at an error occurrence differs depending on the settings of "Input for Err.
Sta" in "Operational settings" of Parameter.
When configuring the settings, consider the station status at errors listed below.
(1) Status of a master station and remote I/O station
The following table shows the status of the master station and remote I/O
stations when an error occurred.
Data link status
Master station
Remote I/O station
Remote input
(RX)
Remote
output
(RY)
Remote
register
(RWw)
Remote register
(RWr)
Input Output
When the local station's programmable controller CPU is
stopped
(data link continues)
All points are set to off
for only the receive
area from the stopped
local station
1
Continue
Continue
Continue Continue
Continue
When data link for
the entire system is
stopped
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear Clear
— — Latch —
All points
off
Hold Latch
When a
communication error
(power off, etc.)
occurs in a remote
I/O station
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear
Clears the receive
area from the remote
I/O station having a
communication error
Continue
Continue
Continue
—
All points
off
Hold
Retains the receive
area from the remote
I/O station having a
communication error
When a
communication error
(power off, etc.)
occurs in a remote
device station
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear
Clears the receive
area from the remote
device station having
a communication error
Continue
Continue
Retains the
receive area
from the remote
device station
having a
communication
error
Continue
Continue
Hold
Retains the receive
area from the remote
device station having
a communication error
When a
communication error
(power off, etc.)
occurs in a local
station
"Input for Err. Sta." of the
CC-Link Ver.2 utility
(for master station setting)
Clear
Clears the receive
area from the local
station having a
communication error
Continue
Continue
Retains the
receive area
from the local
station having a
communication
error
Continue
Continue
Hold
Retains the receive
area from the local
station having a
communication error
1: This is because Yn0 (refresh direction) is turned off.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......