App - 23 App - 23
MELSEC
APPENDIX
Number Name
Description
Availability
( : Available, : Not available)
Online
Offline
Master
station
Local
station
SW0045
(645
H
)
Data link stop
result
Stores the execution result of the data-link stop instruction with
SB0002.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
SW0049
(649
H
)
Temporary error
invalid station
specification result
Indicates the execution result of temporary error invalid station
specification with SB0004.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
SW004B
(64B
H
)
Temporary error
invalid station
specification
cancel result
Indicates the execution result of the temporary error invalid station
specification cancellation with SB0005.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
SW004D
(64D
H
)
Line test result
Indicates the execution result of the line test with SB0008.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
SW004F
(64F
H
)
Parameter setting
test result
Indicates the execution result of the parameter setting test with
SB0009.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
SW0052
(652
H
)
Automatic CC-
Link startup
execution result
Stores the system configuration check result when a new station is
added to a system using an automatic CC-Link startup.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
SW0058
(658
H
)
Detailed LED
display status
Stores the details of the LED display status.
0: OFF
1: ON
LINE(ERROR)
TIME(ERROR)
PRM(ERROR)
M/S(ERROR)
SW(ERROR)
LOCAL
S MST
MST
ERR.
RUN
b15 b14 b13 b12 b11
b8 b7 b6 b5 b4
b2 b1 b0
b3
0
0
0
0
0
0
b9
b10
: Cable is disconnected or the
transmission path is affected by
noise.
: Responses cannot be received from
any station due to the cable being
disconnected or the transmission
path being affected by noise.
: Invalid parameter value
: Duplicate station on the same line
: Setting Error
: Operating as a local station
: Operating as the standby master station
: Operating as the master station
: Error occurrence
: The module is operating normally.
SW0059
(659
H
)
Transmission rate
setting
Stores the contents of the transmission rate setting.
0: Cancel
1: Set
10 Mbps
5 Mbps
2.5 Mbps
625 kbps
156 kbps
b7 b6 b5 b4 b3
b1 b0
b2
0
0
0
0
0
b8
b15
to
SW005D
(65D
H
)
Forced master
switching
instruction result
Stores the execution result of the forced master switching
instruction with SB000C.
0 :
Normal
Other than 0: Stores the error code (refer to Chapter 15).
2
2: Can be used for the standby master station only.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......