6 - 5 6 - 5
MELSEC
6 PARAMETER SETTINGS
6.2 Parameter Setting Examples (Remote Net Ver.1 Mode)
This section explains the parameter settings using the CC-Link Ver.2 utility.
6.2.1 Master station network parameter settings
The descriptions in this section are based on the following system configuration
example.
For details of the CC-Link Ver.2 utility, refer to Section 8.2.
Master station
Q80BD-
J61BT11N
Remote I/O
station
(occupies
1 station)
Local station
QJ61BT11
(occupies
4 stations)
Station
number 1
Ver.1 compatible
remote device
station
(occupies
2 stations)
Station
number 3
Station
number 4
Station
number 8
Remote I/O
station
(occupies
1 station)
Setting item
Setting value
Sta. No.
0
Type
Master station
Transmission rate
10 Mbps
Mode
Remote net [Ver.1 mode]
Operational
settings
Expanded cyclic
single
Occupied Sta.
Occupies 1 station
Input for Err. Sta.
Clear
Other
settings
Retry count
3 (Times)
Automatic reconnection station count
1 (Module)
Standby master station No.
0 (no standby master station designated)
Delay information setting
0 50 micro sec
Driver WDT Monitoring Time
250 8 ms
Block data assurance per station
Disable
Link refresh cycle
----
Station information
settings
All connect count
4 (Modules)
Station information
Refer to the Table below.
Station information setting items
Setting item
Setting value
No. / Sta. No.
1/1
2/3
3/4
4/8
Station type
Remote device
station
Remote I/O station
Intelligent device
station
Remote I/O station
Expanded cyclic
single
single
single
single
Occupied Sta.
Occupies 2 stations
Occupies 1 station
Occupies 4 stations Occupies 1 station
Remote station points
64 points
32 points
128 points
32 points
Reserve/invalid station select
No setting
No setting
No setting
No setting
Intelligent buffer
select (word)
Send
----
---- 16 ----
Receive
----
---- ---- ----
Automatic
----
---- ---- ----
: Setting not required
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......