Address
Item Description
Read/write
possibility
Availability
Reference
Hexadecimal Decimal
Master
station
Local
station
01E0
H
to
02DF
H
480
to
735
Remote register
(RWw)
2
Master station:
For sending
Local station:
For sending/receiving
For the master station: Stores the send data to
the remote device/all local/
intelligent device/standby
master stations.
Write only
—
Appendix 1
(2)
For the local station: Stores the send data to
the master/other local/
intelligent device/standby
master stations.
Also, stores the receive
data from the remote
device/other local/
intelligent device/standby
master stations.
Read/write
enabled
—
02E0
H
to
03DF
H
736
to
991
Remote register
(RWr)
2
Master station:
For receiving
Local station:
For receiving
For the master station: Stores the receive data
from the remote device/
local/intelligent device/
standby master stations.
Read only
—
Appendix 1
(2)
For the local station: Stores the receive data
from the master station.
—
03E0
H
to
05DF
H
992
to
1503
Slave station offset and
size information
Stores offset and size information of
RX/RY/RWw/RWr for each remote station, local
station, intelligent device station, and standby
master station.
Read only
Appendix 1
(5)
05E0
H
to
05FF
H
1504
to
1535
Link special relay (SB) Stores the data link status.
Read/write
enabled
(write may
be disabled
depending
on the
device)
Appendix 1
(3)
0600
H
to
07FF
H
1536
to
2047
Link special register
(SW)
Stores the data link status.
Appendix 1
(4)
0800
H
to
09FF
H
2048
to
2559
Use prohibited
1
— —
—
—
—
0A00
H
to
0FFF
H
2560
to
4095
Random access buffer
The specified data is stored and used by
transient transmission.
Read/write
enabled
Appendix 1
(6)
1000
H
to
1FFF
H
4096
to
8191
Use prohibited
1
— —
—
—
—
2000
H
to
2FFF
H
8192
to
12287
Automatic update
buffer
Stores the automatic update data when
performing transient transmission with the
AJ65BT-R2 (communication using the
automatic update buffer).
Read/write
enabled
Appendix 1
(7)
3000
H
to
3FFF
H
12288
to
16383
Use prohibited
1
— —
—
—
—
: Available, — : Not available
1: Do not write to any area where use is prohibited. This may cause errors.
2: Used when the remote net ver.1 mode or remote net additional mode is selected.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......