4 - 45 4 - 45
MELSEC
4 FUNCTIONS
4.4.7 Increasing the number of cyclic points (Remote net ver.2 mode, Remote net additional
mode)
This function increases the number of cyclic points in the CC-Link system.
When increasing the number of cyclic points, select one from the following two modes.
Remote net ver.2 mode ................... Mode used for configuring a new system
Remote net additional mode............ Mode used for incorporating an additional Ver.2
compatible slave station into the existing Ver.1
system
The number of cyclic points per station can be increased as indicated in the following
table.
Table 4.7
Expanded cyclic setting
single double
quadruple
octuple
Occupies 1 station
Remote I/O (RX, RY)
32 points
32 points
64 points
128 points
Remote register (RWw, RWr)
4 points
8 points
16 points
32 points
Occupies 2 stations
Remote I/O (RX, RY)
64 points
96 points
192 points
384 points
Remote register (RWw, RWr)
8 points
16 points
32 points
64 points
Occupies 3 stations
Remote I/O (RX, RY)
96 points
160 points
320 points
640 points
Remote register (RWw, RWr)
12 points
24 points
48 points
96 points
Occupies 4 stations
Remote I/O (RX, RY)
128 points
224 points
448 points
896 points
Remote register (RWw, RWr)
16 points
32 points
64 points
128 points
REMARK
In the remote net ver.1 mode, the number of cyclic points cannot be increased.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......