5 - 14 5 - 14
MELSEC
5 PROCEDURE BEFORE STARTING THE DATA LINK
5.5 Station Number Setting
The following explains how to set the station numbers for the master station, local
station, standby master station, remote station and intelligent device station.
For details on the station number settings, refer to Section 8.2.3.
Specify the station numbers according to the following conditions:
(1) Assign sequential station numbers.
Station numbers can be specified regardless of the order in which the stations are
connected.
For a module occupying two or more stations, specify the first station number.
(2) Specify unused station numbers as reserved stations.
If unused station numbers are not specified as reserved stations, they will be
handled as data link faulty stations (can be checked with special link registers
SW0080 to SW0083).
(3) Specify unique station numbers.
If duplicate station numbers are specified, an installation error occurs. (Error
codes are stored in SW0069)
[Setting example] One station was skipped when station numbers were specified.
St. No. 4
5) Local station
3) Standby master station
2) Remote device station
1) Remote
I/O station
Data link faulty station
(If this station was specified as a reserve station,
it would not have been treated as a faulty station.)
1)
Remote I/O station
(occupies 1 station)
2) Remote device
station
(occupies 2 stations)
Master
station
3)
Standby
master station
(occupies
4 stations)
5)
Local station
(occupies
1 station)
4) Intelligent
device station
(occupies 1 station)
Station
number "0"
Intelligent
device
station
4)
Station
number "1"
Station
number "2"
Station
number "5"
Station
number "9"
Station
number "10"
St. No. 3
St. No. 2
St. No. 1
St. No. 5
St. No. 6
St. No. 7
St. No. 8
St. No. 9
St. No. 10
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......