App - 22 App - 22
MELSEC
APPENDIX
Appendix 2.2 List of link special registers (SWs)
The data link status can be checked by the word information (link special registers: SWs).
When the standby master station is controlling the data link, availability is basically
identical to that of the master station.
When the standby master station is operating as a local station, availability is identical
to that of a local station.
Number Name
Description
Availability
( : Available, : Not available)
Online
Offline
Master
station
Local
station
SW0003
(603
H
)
Multiple temporary
error invalid
station
specification
Select whether multiple temporary error invalid stations are
specified.
00
: Specifies multiple stations indicated by SW0004 to
SW0007.
01 to 64: Specifies a single station from 1 to 64.
(The specified number indicates the station number of a
temporary error invalid station.)
SW0004
(604
H
)
SW0005
(605
H
)
SW0006
(606
H
)
SW0007
(607
H
)
Temporary error
invalid station
specification
1
Specifies a temporary error invalid station.
0: Not specified as a temporary error invalid station
1: Specified as a temporary error invalid station
16
15
14
13
4
3
2
1
48
47
46
45
36
35
34
33
32
31
30
29
20
19
18
17
64
63
62
61
52
51
50
49
b15
b14
b13
b12
to
b3
b2
b1
b0
SW0004
SW0005
SW0006
SW0007
Numbers 1 to 64 in the above table indicate the station numbers.
to
to
to
to
SW0008
(608
H
)
Line test station
setting
Sets the station for which line tests are executed.
0
: Entire system (executed for all stations)
01 to 64
: Specified station only
Default value : 0
SW0009
(609
H
)
Monitoring time
setting
Sets the monitoring time when a dedicated instruction is used.
Default value : 10 (seconds)
Setting range : 0 to 360 (seconds)
The monitoring time of 360 seconds will be used if a value
outside of the above setting range is specified.
SW000A
(60A
H
)
CPU monitoring
time setting
Sets the CPU response monitoring time when the CPU is accessed
with a dedicated instruction.
Default value : 90 (seconds)
Setting range : 0 to 3600 (seconds)
The monitoring time of 3600 seconds will be used if a value
outside of the above setting range is specified.
SW0020
(620
H
)
Module status
Stores the communication status between CC-Link Ver.2 board and
personal computer.
0 :
Normal
Other than 0 : Stores the error code
(refer to MELSEC Data Link Library Reference Manual).
SW0041
(641
H
)
Data link restart
result
Stores the execution result of the data link restart instruction with
SB0000.
0 :
Normal
Other than 0 : Stores the error code (refer to Chapter 15).
SW0043
(643
H
)
Refresh
instruction at
standby master
switching result
Indicates the execution result of refresh instruction at standby
master switching.
0 :
Normal
Other than 0 : Stores the error code (refer to Chapter 15).
1: Only the bit for the first station number is turned on.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...
Page 124: ...5 16 5 16 MELSEC 5 PROCEDURE BEFORE STARTING THE DATA LINK MEMO ...
Page 160: ...9 2 9 2 MELSEC 9 MELSEC DATA LINK LIBRARY MEMO 9 ...
Page 200: ...12 16 12 16 MELSEC 12 COMMUNICATION BETWEEN THE MASTER STATION AND LOCAL STATIONS MEMO ...
Page 355: ...App 93 App 93 MELSEC APPENDIX MEMO ...
Page 361: ......