15 ERROR CODE
Detectability
Error code
(hexadecimal)
Error description
Cause of error (details)
Corrective action
Master
station
Local
station
BA1B
All stations error
All stations stopped communications
during line test.
Check the cables.
BBC1
Mode setting error
The mode setting of a local station is
not set to "1."
Set "0."
BBC2
Station number setting
error
The station number setting is set to a
value "other than 0 to 64."
Set the value within the range
from "0 to 64."
BBC3
Transmission rate
setting error
The transmission rate setting is set to a
value "other than 0 to 4."
Set the value within the range
from "0 to 4."
BBC5
Master station duplicate
error
A master station already exists.
Review the station number
setting switch.
BBC7
Module error
The module is faulty.
Replace the module.