CC-Link Ver.2 Board
2) Reads out the initial data processing request flag
(RX18).
3) With the initial data processing request flag (RX18)
ON, writes data to the analog output enable/disable
setting area (RWw8).
5) Turns ON the initial data processing completion
flag (RY18).
4) Writes data to the analog output enable/disable
setting area (RWw8) on the AJ65VBTCU-68DAV.
6) Turns ON the initial data processing completion
flag (RY18) on the AJ65VBTCU-68DAV.
7) The initial data processing request flag (RX18) is
turned OFF on the AJ65VBTCU-68DAV.
1) Turns ON the initial data processing request flag
(RX18) on the AJ65VBTCU-68DAV after turning
on the AJ65VBTCU-68DAV.
8) Reads out the initial data processing request flag
(RX18).
9) With the initial data processing request flag (RX18)
OFF, turns OFF the initial data processing
completion flag (RY18).
10) Turns OFF the initial data processing completion
flag (RY18) on the AJ65VBTCU-68DAV.
11) Turns ON the initial data setting request flag
(RY19).
12) Turns ON the initial data setting request flag
(RY19) on the AJ65VBTCU-68DAV.
13) The initial data setting completion flag (RX19) on
the AJ65VBTCU-68DAV is turned ON.
14) Reads out the initial data setting completion flag
(RX19).
15) With the initial data setting completion flag (RX19)
ON, turns OFF the initial data setting request flag
(RY19).
16) Turns OFF the initial data setting request flag
(RY19) on the AJ65VBTCU-68DAV.
17) The initial data setting completion flag (RX19) on
the AJ65VBTCU-68DAV is turned OFF, and the
remote READY (RX1B) is turned ON.
18) Reads out the initial data setting completion flag
(RX19) and the remote READY (RX1B).
19) With the initial data setting completion flag (RX19)
OFF and the remote READY (RX1B) ON, perform
the following:
Writing digital values to the CH1 digital value
setting area (RWw0).
Turning ON the analog output enable flag
(RY00) of the channel.
20) Writes digital values to the CH1 digital value
setting area (RWw0) on the AJ65VBTCU-68DAV.
Analog values are output from the AJ65VBTCU-
68DAV.
Summary of Contents for Q80BD-J61BT11N
Page 2: ......
Page 34: ...1 10 1 10 MELSEC 1 OVERVIEW MEMO ...
Page 54: ...3 12 3 12 MELSEC 3 SPECIFICATIONS MEMO ...