5 INSTALLATION AND WIRING
5.1 Setting Switch
■
Number of AnyWireASLINK bit points setting
Set the number of AnyWireASLINK bit points.
■
Number of AnyWireASLINK word points setting
Set the number of AnyWireASLINK word points.
• Do not change the MODE switch while the NZ2AW1GNAL is in the power-on state. If the MODE switch is
changed while the NZ2AW1GNAL is in the power-on state, MODE switch 1 change error (error code:
1041H) to MODE switch 12 change error (error code: 104CH) will occur, and the MODE switch change will
not be reflected. After returning the MODE switch to its original state, turn off and on Error reset request flag
(RY0) to recover from the error.
• When the number of points is set using the MODE switch, the information set by the switch (number of bit
points, number of word points, number of word points per frame) is not reflected in the non-volatile memory,
and only the parameter area (0000H to 01FFH) and the monitor area (0200H to 03FFH) are reflected.
• When the number of transmission points of AnyWireASLINK setting is on, if the CC-Link IE TSN parameter
processing of a slave station is performed using the engineering tool or if the number of AnyWireASLINK
points is set with the program, Number of transmission points of AnyWireASLINK setting error (error code:
1021H) occurs. However, writing can be performed to the parameter area of the remote buffer memory
(0000H to 01FFH). The operation of the NZ2AW1GNAL follows the setting value of MODE switch 2.
• When the number of transmission points of AnyWireASLINK setting is on but the number of
AnyWireASLINK bit points is set to 0 or the number of AnyWireASLINK word points is set to 0, Transmission
points setting error (error code: 180CH) occurs.
• If the number of AnyWireASLINK word points is set to 0, 0000H (no word data) is stored in Word data use
setting (0101H) of the remote buffer memory. If set to anything other than 0, 0001H (use) is stored.
MODE switch 3
MODE switch 4
MODE switch 5
Number of AnyWireASLINK bit points
Off
Off
Off
0 points (0 input points/0 output points)
On
Off
Off
64 points (32 input points/32 output points)
Off
On
Off
128 points (64 input points/64 output points)
On
On
Off
256 points (128 input points/128 output points)
Off
Off
On
512 points (256 input points/256 output points)
On
Off
On
1024 points (512 input points/512 output points)
Off
On
On
Setting prohibited
On
On
On
Setting prohibited
MODE switch 6
MODE switch 7
MODE switch 8
Number of word
points per frame
Number of AnyWireASLINK word points
Off
Off
Off
0
0 words (0 input words/0 output words)
On
Off
Off
4
16 words (8 input words/8 output words)
Off
On
Off
4
64 words (32 input words/32 output words)
On
On
Off
16
128 words (64 input words/64 output words)
Off
Off
On
16
256 words (128 input words/128 output words)
On
Off
On
32
512 words (256 input words/256 output words)
Off
On
On
32
1024 words (512 input words/512 output words)
On
On
On
Setting prohibited
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......