![Mitsubishi Electric AnyWire ASLINK User Manual Download Page 26](http://html.mh-extra.com/html/mitsubishi-electric/anywire-aslink/anywire-aslink_user-manual_238818026.webp)
24
5 INSTALLATION AND WIRING
5.1 Setting Switch
Setting range
Set the value from 1 to 254.
When the value from 1 to 254 is set, the result is as follows.
• IP address: The first to third octet operate in the first to third octet of the IP address of the master station.
• Subnet mask: Operates with the subnet mask of the master station.
If a value other than 1 to 254 is set, the following will occur.
• If 0 is set, the IP address saved in the non-volatile memory and the subnet mask of the master station will be used in
operation.
• If 255 is set, IP address setting switch range error (error code: 2400H) occurs. At this time, the IP address is 192.168.3.250
and the subnet mask is 255.255.2555.0 (fixed).
• Do not change the IP address setting switch while the NZ2AW1GNAL is in the power-on state. If the IP
address setting switch is changed while the NZ2AW1GNAL is in the power-on state, IP address setting
switch change error (error code: 1030H) occurs and the ERR. LED flashes. After returning the IP address
setting switch to the original position, turned off and on Error reset request flag (RY0) to recover from the
error status, and the ERR. LED turns off.
• If the power is turned on while the IP address setting switch is 1 to 254, the IP address is saved in the non-
volatile memory when data link is performed with the master station. As the factory default, 192.168.3.250 is
set for the non-volatile memory.
• Set the IP address in a way that the fourth octet is not duplicated in the access range of CC-Link IE TSN. If
duplicated, the IP address will be duplicated due to the automatic setting of the first to third octet of the IP
address, and data link will not be established.
The following IP addresses and subnet masks cannot be used for the NZ2AW1GNAL.
• IP address whose host address is all 0 or all 255
• IP address whose third octet and fourth octet are all 255
• IP address whose range is outside 0.0.0.1 to 223.255.255.254
• Subnet mask of 0.0.0.0
• Subnet mask in which 1 is not arranged consecutively on the upper side and 0 is not arranged consecutively
on the lower side when expressed in binary
Precautions
When operating the switch, use a static eliminating product or antistatic driver or touch a conducting object such as a
grounded metal to discharge the static electricity from the human body. Failure to do so may cause the module to fail or
malfunction.
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......