APPX
Appendix 3 Remote Buffer Memory
155
A
Disconnection error automatic recovery mode setting
■
Address
■
Description
Set whether to automatically recover from the alarm status.
The relationship between setting and setting value is as follows.
The alarm that automatically recovers is DP/DN disconnection error (alarm code: 0D00H).
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Disconnection error
automatic recovery mode setting range error (error code: 1808H) is displayed. Also, the setting will not be reflected in the non-
volatile memory.
Word input data hold/clear setting when disconnection occurs
■
Address
■
Description
Set whether to clear or retain the word input data when the word slave module is disconnected.
The relationship between setting and setting value is as follows.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Word input data
hold/clear setting when disconnection occurs range error (error code: 1809H) is displayed. Also, the setting will not be
reflected in the non-volatile memory.
Name
Address
Disconnection error automatic recovery mode setting
0109H
Setting
Setting value
No disconnection error automatic recovery
0000H (initial value)
Disconnection error automatic recovery
0001H
Name
Address
Word input data hold/clear setting when disconnected
010AH
Setting
Setting value
Clear word input when disconnection occurs
0000H (initial value)
Hold word input when disconnection occurs
0001H
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......