180BH
Minor error
Easy replacement
setting for one slave
module range error
The value being set is outside the
settable range for the easy replacement
setting for one slave module.
Change Easy replacement setting for one slave
module (address: 010CH) to a setting value within
the settable range, and turn on Module parameter
reflection request flag (RYC).
180CH
Minor error
Transmission points
setting error
The value being set to Bit data points
setting (remote buffer memory address:
0100H) is 0 points (no bit data)
(000AH), and Word data usage setting
(address: 0102H) is set to Do not use
word data (0000H).
Change either or both of the following settings, and
turn on Module parameter reflection request flag
(RYC).
1. Bit data points setting (address: 0100H) to other
than 0 points (no bit data) (000AH)
2. Word data use setting (address: 0101H) to Use
word data (0001H)
180DH
Minor error
Word data setting
combination error
Setting values that cannot be combined
in regards to "Word data use setting",
"Word data points setting", "Word data
start address setting", and "Word data
points setting per frame" are being set.
On the "Parameter of Slave Station" window, review
whether "Word data use setting", "Word data points
setting", "Word data start address setting", and
"Word data points setting per frame" are consistent.
D010H
Minor error
IP address
duplication
detection
A duplicate IP address has been
detected.
Change the IP address so that no IP addresses are
duplicated in the access range of CC-Link IE TSN.
After the change, power off and on the module
power supply.
2010H
Moderate error
Non-volatile
memory data error
(parameter)
The parameter data saved in the non-
volatile memory is faulty.
• After changing Parameter area initialization
command (address: 0402H) from No command (0)
to Command (1) and back to No command (0),
turn the module power supply off and on to set the
parameters in non-volatile memory to the default
values. Then, set the parameters again.
• Take measures to reduce noise.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
2011H
Moderate error
Non-volatile
memory data error
(IP address)
The IP address and subnet mask saved
in the non-volatile memory are faulty.
• Immediately after the error occurs, it is
automatically restored. However, the saved IP
address and subnet mask are lost, and the system
operates as though the following were saved.
IP address: 192.168.3.250
Subnet mask: 255.255.255.0
• Take measures to reduce noise.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
2400H
Moderate error
IP address setting
switch range error
The IP address setting switch is set to
255.
Turn on the power with the IP address setting switch
set to a value from 0 to 254.
2500H
Moderate error
Module power
supply voltage drop
error
The module power supply voltage has
dropped.
• Check the status of the module power supply.
• Check that the power supply meets the
NZ2AW1GNAL specifications.
3000H
Moderate error
Non-volatile
memory access
error (slave module
information)
An error was detected when accessing
the non-volatile memory that stores
slave module information.
• Power off and on the module power supply.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
3C00H
Major error
Hardware error
The module has a hardware error.
• Power off and on the module power supply.
• If the error occurs again, the module may be in
failure. Please consult your local Mitsubishi
representative.
Error code
(hexadecimal)
Classification
Error name
Error description and cause
Action
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......