Appendix 3 Remote Buffer Memory
Details of buffer memory addresses
Bit data points setting
■
Address
■
Description
Set the total number of input/output points for bit data to be used.
The relationship between setting and setting value is as follows.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Bit data points
setting range error (error code: 1801H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
If Module parameter reflection request flag (RYC) is turned on after writing 000AH (0 points (0 input points/0 output points)) to
Bit data points setting (address: 0100H), and writing 0000H (Not Use) to Word data use setting (address: 0101H),
Transmission points setting error (error code: 180CH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
Name
Address
Bit data points setting
0100H
Setting
Setting value
64 points (32 input points/32 output points)
0000H
128 points (64 input points/64 output points)
0001H
256 points (128 input points/128 output points)
0002H
512 points (256 input points/256 output points)
0003H (initial value)
1024 points (512 input points/512 output points)
0004H
0 points (0 input points/0 output points)
000AH
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......