7 FUNCTIONS
7.2 Remote Address Change Function
Precautions
• Before changing the remote address, perform automatic address detection and check that it completes without any errors.
• After changing the remote address, perform automatic address detection. However, when changing multiple IDs, perform
automatic address detection after completing all of them.
• This function cannot be executed for slave modules separated from the NZ2AW1GNAL because of disconnection or slave
modules having the same ID. For slave modules that have the same IDs, use an address writer to change the IDs of the
slave modules.
• This function can be executed if only one slave module having no ID exists within one AnyWireASLINK line. If IDs of
multiple slave modules are not set, the ID would be duplicated, so the IDs cannot be changed.
• If a slave module cannot be set to a word address, do not change to the ID of a word output, word input, or word I/O
combined slave module. By doing so, a New ID error (alarm code: 0D92H) will occur in NZ2AW1GNAL.
• Do not set addresses 256 to 510 for slave modules that do not support 1024 points of bit data. If set, a New ID error (alarm
code: 0D92H) will occur in NZ2AW1GNAL.
• The conditions where the remote address change function cannot be executed are the same as for slave module
parameter read/write. For details, refer to the following.
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......