6 CONFIGURATION
6.2 Parameter Setting
43
6
*1 This item can be set when "Word data use setting" is set to "1: Use".
*2 This item can be set when "Word data points setting" is set within the range from "2: 4 words (input 2 words, output 2 words)" to "10:
1024 words (input 512 words, output 512 words)".
*3 This item can be set when "Word data points setting" is set within the range from "3: 8 words (input 4 words, output 4 words)" to "10:
1024 words (input 512 words, output 512 words)".
*4 This item can be set when "Word data points setting" is set within the range from "4: 16 words (input 8 words, output 8 words)" to "10:
1024 words (input 512 words, output 512 words)".
*5 This item can be set when "Word data points setting" is set within the range from "5: 32 words (input 16 words, output 16 words)" to "10:
1024 words (input 512 words, output 512 words)".
If a value outside the set range is written to the module parameter area (0000H to 01FFH) of the remote buffer
memory, when parameter reading is executed on the "Parameter of Slave Station" window of the CC-Link IE
TSN configuration window, the value displayed will be as follows.
• Word data start address setting (0103H): Set value
• Other than Word data start address setting (0103H): Invalid value
Double verification
setting
Set the bit data double verification mode. (
• 0: All points, double verification of a bit
• 1: Double verification of the 16 bit (word) until the 1st word
• 2: Double verification of the 16 bit (word) until the 2nd word
• 3: Double verification of the 16 bit (word) until the 3rd word
• 4: Double verification of the 16 bit (word) until the 4th word
• 5: Double verification of the 16 bit (word) until the 5th word
• 6: Double verification of the 16 bit (word) until the 6th word
• 7: Double verification of the 16 bit (word) until the 7th word
• 8: Double verification of the 16 bit (word) until the 8th word
• 9: Double verification of the 16 bit (word) until the 9th word
• 10: Double verification of the 16 bit (word) until the 10th word
• 11: Double verification of the 16 bit (word) until the 11th word
• 12: Double verification of the 16 bit (word) until the 12th word
• 13: Double verification of the 16 bit (word) until the 13th word
• 14: Double verification of the 16 bit (word) until the 14th word
• 15: Double verification of the 16 bit (word) until the 15th word
• 16: Double verification of the 16 bit (word) until the 16th word
• 17: Double verification of the 16 bit (word) until the 17th word
• 18: Double verification of the 16 bit (word) until the 18th word
• 19: Double verification of the 16 bit (word) until the 19th word
• 20: Double verification of the 16 bit (word) until the 20th word
• 21: Double verification of the 16 bit (word) until the 21st word
• 22: Double verification of the 16 bit (word) until the 22nd
word
• 23: Double verification of the 16 bit (word) until the 23rd word
• 24: Double verification of the 16 bit (word) until the 24th word
• 25: Double verification of the 16 bit (word) until the 25th word
• 26: Double verification of the 16 bit (word) until the 26th word
• 27: Double verification of the 16 bit (word) until the 27th word
• 28: Double verification of the 16 bit (word) until the 28th word
• 29: Double verification of the 16 bit (word) until the 29th word
• 30: Double verification of the 16 bit (word) until the 30th word
• 31: Double verification of the 16 bit (word) until the 31st word
• 32: All points, double verification of the 16 bit (word)
(Default: 0: All points, double verification of a bit)
Disconnection error
automatic recovery
mode setting
Set the disconnection error automatic recovery mode. (
66 Disconnection Error Automatic Recovery Function)
• 0: No disconnection error automatic recovery
• 1: Disconnection error automatic recovery
(Default: 0: No disconnection error automatic recovery)
Word input data hold/
clear setting when
disconnected
Set whether to hold or clear the word input data when a
disconnection occurs.
• 0: CLEAR
• 1: HOLD
(Default: 0: CLEAR)
Output data hold/clear
setting
Set whether to hold or clear the output data when an error occurs.
• 0: CLEAR
• 1: HOLD
(Default: 0: CLEAR)
Single module
simplified replacement
Enable or disable easy replacement setting for one slave module.
• 0: Enable
• 1: Disable
(Default: 0: Enable)
Item
Setting
Setting range
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......