APPX
Appendix 3 Remote Buffer Memory
157
A
Word transmission cycle time
■
Address
■
Description
These areas are for checking the word transmission cycle time of AnyWireASLINK.
These areas store 32-bit integers. (Unit: 0.1ms, rounded up to the 2nd decimal point)
For details on the calculation formula of the word transmission cycle time, refer to the following.
Page 178 Transmission cycle time formula
Bit data points setting value
■
Address
■
Description
This area is for checking the bit point settings of AnyWireASLINK.
The relationship between monitor value and number of bit points is as follows.
Word data use setting value
■
Address
■
Description
This area is for checking whether word transmission is used.
The relationship between monitor value and number of word points is as follows.
Name
Address
Word transmission cycle time
020CH to 020DH
020CH (524)
020DH (525)
Upper
Lower
Name
Address
Bit data points setting value
0310H
Monitor value
Number of bit points
0000H
64 points (32 input points/32 output points)
0001H
128 points (64 input points/64 output points)
0002H
256 points (128 input points/128 output points)
0003H
512 points (256 input points/256 output points)
0004H
1024 points (512 input points/512 output points)
000AH
0 points (No bit data)
Name
Address
Word data use setting value
0311H
Monitor value
Number of word points
0000H
Not use word transmission
0001H
Use word transmission
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......