10 TROUBLESHOOTING
10.3 Unit Test
113
10
10.3
Unit Test
This function checks the module hardware when communication using the NZ2AW1GNAL is unstable.
1.
Turn off the power of the NZ2AW1GNAL.
2.
Connect P1 and P2 of the NZ2AW1GNAL with an Ethernet cable.
3.
Set the IP address setting switch and MODE switch as follows.
• IP address setting switch (x1): Any value
• IP address setting switch (x16): F
• MODE switch 1: ON
• MODE switch 2 to MODE switch 12: Any value
4.
Turn on the power of the NZ2AW1GNAL.
5.
The unit test starts.
During the unit test, the RUN LED flashes and the D LINK LED turns off.
AnyWireASLINK transmission stops during unit test execution. Also, changing the IP address setting switch or MODE switch
will be ignored.
6.
When the unit test is completed, the RUN LED turns off and the D LINK LED turns on.
• When completed successfully, the ERR. LED remains off and does not turn on.
• When completed with an error, the ERR. LED turns on. If the unit test is completed with an error, replace the Ethernet cable
and re-execute the unit test. If the test is completed with an error again, a hardware error of the NZ2AW1GNAL is likely.
Please consult your local Mitsubishi representative.