10 TROUBLESHOOTING
10.4 Troubleshooting by Symptom
When the AnyWireASLINK version compatibility inspection
cannot be executed
When the AnyWireASLINK version compatibility inspection cannot be executed, check the following items.
When the remote address cannot be changed
When the remote address cannot be changed, check the following items.
Check item
Action
Is Word data usage setting on the NZ2AW1GNAL enabled?
Set the word data points setting of the NZ2AW1GNAL to 2 words (1 input word/1 output
word) or larger, and execute the AnyWireASLINK version compatibility inspection again.
Has an error that prevents execution of the AnyWireASLINK
version compatibility inspection occurred?
Eliminate errors other than an AnyWireASLINK version compatibility inspection error, and
execute the AnyWireASLINK version compatibility inspection again.
Is a slave module with a duplicate ID connected?
Change the address of the slave module so that the ID is not duplicated, and execute the
AnyWireASLINK version compatibility inspection again.
Are more slave modules than the maximum number of
connectable modules connected?
Reduce the number of connected slave modules to the maximum number of connectable
modules or less, and execute the AnyWireASLINK version compatibility inspection again.
Check item
Action
Has automatic address detection been performed?
Change the remote address after performing automatic address detection.
Is a slave module with a duplicate ID connected?
Change the address of the slave module so that the ID is not duplicated, and perform
automatic address detection. Then, change the remote address again.
Does the slave module support remote address change?
Replace the slave module with one that supports remote address change, and change the
remote address again.
For details on whether a slave module supports remote address change, refer to the
manual for each slave module used.
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......