16
2 SPECIFICATIONS
2.2 Performance Specifications
2.2
Performance Specifications
The following table lists the performance specifications.
*1 For the number of points used in the NZ2AW1GNAL, refer to the following.
*2 For the network topology, follow the specifications of the master station used.
*3 For wiring of 50m or more with 4 wires (DP, DN, 24V, 0V), insert the noise filter for power supply cables between the power supply and
cables. For details, refer to the manual for the AnyWireFILTER (ANF-01) manufactured by Anywire Corporation.
*4 For the relationship between the total length, the wire diameter of transmission cables (DP, DN), and the transmission cable supply
current, refer to the following. On some slave modules with cables, the wire diameter of module-integrated transmission cables (DP, DN)
may be 0.75
or less. However, they can be used without any problem, provided that the diameter of the transmission cables (DP,
DN) meets the requirement below.
*5 When the 24VDC power is supplied from the NZ2AW1GNAL to slave modules, ensure that the total amount of the transmission cable
supply current and the current supplied to slave modules does not exceed 2A.
Classification
Item
Specifications
CC-Link IE TSN
Station type
Remote station
Authentication Class
Authentication Class B
Maximum number of link points
Remote input (RX)
544 points
Remote output (RY)
544 points
Remote register (RWw)
544 words
Remote register (RWr)
544 words
Network topology
Line topology, star topology, coexistence of line and star topologies, ring topology
AnyWireASLINK
Transmission clock
27.0kHz
Maximum transmission distance
(total length)
200m
Transmission method
DC power supply superimposed total frame/cyclic method
Connection type
Bus topology (multidrop system, T-branch system, tree branch system)
Transmission protocol
Dedicated protocol (AnyWireASLINK)
Error control
Checksum, double-verification system
Number of bit data points
1024 points maximum (input: 512 points, output: 512 points)
Number of word data points
1024 points maximum (input: 512 points, output: 512 points)
Number of connected slave
modules
256 maximum (varies depending on the current consumption of each slave module)
RAS function
Disconnected transmission cable location detection function, transmission cable short detection
function, module power supply drop detection function
AnyWireASLINK transmission
cable
24VDC power cable
• UL-listed general-purpose 2-wire cable (VCTF, VCT 1.25
, 0.75
, temperature rating 70
or higher)
• UL-listed general-purpose wire (1.25
, 0.75
, temperature rating 70
or higher)
• Dedicated flat cable (1.25
, 0.75
, temperature rating 90
)
Transmission cable supply
current
2A maximum
Common
Power supply
Voltage: 21.6 to 27.6VDC (24VDC -10 to +15%), ripple 0.5Vp-p or lower
Recommended voltage: 26.4VDC (24VDC + 10%)
Module current consumption: 0.2A
External dimensions
102mm(H)
43mm(W)
102.8mm(D)
Weight
0.2kg
Wire diameter of transmission
cables (DP, DN)
Transmission cable supply current
Total length of 50m or less
Total length of 50m to 100m
Total length of 100m to 200m
1.25
2A maximum
1A maximum
0.5A maximum
0.75
1.2A maximum
0.6A maximum
0.3A maximum
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......