5 INSTALLATION AND WIRING
5.9 Powering on the System
39
5
5.9
Powering on the System
After checking the items described above, power on and start the system.
How to power on the AnyWireASLINK system is as follows.
The order is inverted when the system is powered off.
1.
24VDC external power supply for the AnyWireASLINK system
(This step is required only when the supply power of slave module is different from power supply of the NZ2AW1GNAL. When
the supply power is same as the NZ2AW1GNAL, this step is not required.)
2.
Module power supply of the NZ2AW1GNAL
3.
Power supply of the programmable controller
• Supply the power according to the steps: (1) 24VDC external power supply of AnyWireASLINK system, (2)
the NZ2AW1GNAL, (3) the programmable controller, or turn them on at the same time.
• If the NZ2AW1GNAL is powered on before the 24VDC external power supply in the AnyWireASLINK
system, a DP/DN disconnection error may occur.
• After Remote READY (RX0) turns on, wait at least one second to start the program.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Module power supply of
the NZ2AW1GNAL
Remote READY
AnyWireASLINK system
24VDC external power supply
Program
1 second
or longer
Power supply of
the programmable controller
Summary of Contents for AnyWire ASLINK