APPX
Appendix 3 Remote Buffer Memory
151
A
Word data use setting
■
Address
■
Description
Set whether to use the word data.
The relationship between setting and setting value is as follows.
If Module parameter reflection request flag (RYC) is turned on after writing anything other than the above, Word data use
setting range error (error code: 1802H) is displayed. Also, the setting will not be reflected in the non-volatile memory.
If Word data points setting (address: 0102H) is 0000H (Not Use), set this setting to 0000H (Not Use) also.
If Module parameter reflection request flag (RYC) is turned on after writing 000AH (0 points (0 input points/0 output points)) to
Bit data points setting (address: 0100H), and writing 0000H (Not Use) to Word data use setting (address: 0101H),
Transmission points setting error (error code: 180CH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
If Module parameter reflection request flag (RYC) is turned on after writing a combination other than the one that can be set,
Word data setting combination error (error code: 180DH) is displayed. Also, the setting will not be reflected in the non-volatile
memory.
The combinations that can be set are as follows.
Name
Address
Word data use setting
0101H
Setting
Setting value
Not use
0000H (initial value)
Use
0001H
Word data use
setting
Word data points setting
Word data start
address setting
Word data points setting per frame
0: Not use
0: Not use
0
0: Not use
1: Use
1: 2 words (input 1 word, output 1 word)
0 to 511
1: 2 words (input 1 word, output 1 word)
2: 4 words (input 2 words, output 2 words)
0 to 511
1: 2 words (input 1 word, output 1 word)
2: 4 words (input 2 words, output 2 words)
3: 8 words (input 4 words, output 4 words)
0 to 511
1: 2 words (input 1 word, output 1 word)
2: 4 words (input 2 words, output 2 words)
3: 8 words (input 4 words, output 4 words)
4: 16 words (input 8 words, output 8 words)
0 to 511
1: 2 words (input 1 word, output 1 word)
2: 4 words (input 2 words, output 2 words)
3: 8 words (input 4 words, output 4 words)
4: 16 words (input 8 words, output 8 words)
5: 32 words (input 16 words, output 16 words)
6: 64 words (input 32 words, output 32 words)
7: 128 words (input 64 words, output 64 words)
8: 256 words (input 128 words, output 128 words)
9: 512 words (input 256 words, output 256 words)
10: 1024 words (input 512 words, output 512 words)
0 to 511
1: 2 words (input 1 word, output 1 word)
2: 4 words (input 2 words, output 2 words)
3: 8 words (input 4 words, output 4 words)
4: 16 words (input 8 words, output 8 words)
5: 32 words (input 16 words, output 16 words)
Summary of Contents for AnyWire ASLINK
Page 1: ...CC Link IE TSN AnyWireASLINK Bridge Module User s Manual NZ2AW1GNAL ...
Page 2: ......
Page 22: ...20 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 96: ...94 8 PROGRAMMING 8 2 Program Example Program ...
Page 100: ...98 8 PROGRAMMING 8 2 Program Example Program ...
Page 101: ...8 PROGRAMMING 8 2 Program Example 99 8 ...
Page 199: ......