47LLC OPERATING MANUAL EM-9505-B Rev.4
10.1 OPERATING PROCEDURE
NOTE
•
Procedures to change ‘DISP’ to ‘SCLE’ are described
here.
•
To change ‘SCLE’ to ‘DISP’, the procedures are same.
Select ‘DISP’ in Step 3.
1
Hold down Scale/
↑
button for 3 seconds or more to move on to
Scaling Setting Mode.
•
The input type is indicated.
•
‘Zro’ and ‘Spn’ indicators turn on.
2
Press Alarm/
↓
or Scale/
↑
button to go to the analog output
function mode setting.
•
‘DISP’ is indicated.
•
‘Fnc’ indicator turns on.
3
Press Shift or Up button to select ‘SCLE’.
4
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
•
And the next parameter setting is indicated.
NOTE
•
Press Alarm/
↓
button, and the analog output 0% adjustment ‘ADJ’ will be indicated.
•
Press Scale/
↑
button, and the decimal point position will be indicated.
5
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.
2,4,
5
1,2,
4,5
3
3
Blinking