128
47LLC OPERATING MANUAL EM-9505-B Rev.4
18.3 LIMITING BUTTON OPERATION
Transition from Measuring Mode to each setting mode or Loop Test Output Mode can be limited. With this setting, the
transition to each mode by holding down the buttons will be disabled. In Lockout Setting Mode, the lockout per mode is
selectable.
■
LOCKOUT sETTING
Following 4 lockout settings are available.
PARAMETER
INDICATORS
DISPLAY
FUNCTION
DEFAULT VALUE
Alarm setting lockout
D/P, Fnc
Unlock Alarm Setting Mode
Lock Alarm Setting Mode
Scaling setting lockout
Unlock Scaling Setting Mode
Lock Scaling Setting Mode
Advanced setting lockout
Unlock Advanced Setting Mode
Lock Advanced Setting Mode
Loop test output lockout
Unlock Loop Test Output Mode
Lock Loop Test Output Mode
18.3.1 OPERATING PROCEDURE
NOTE
•
Procedures to lock the advanced setting mode are
described here. The procedures to lock other setting
modes are same. Select your desired mode to lock in
Step 2.
•
To cancel the limitation, select ‘xOFF’ in Step 3.
1
Hold down Max/Min and Alarm/
↓
buttons at once for a preset
time duration to move on to Lockout Setting Mode.
•
The alarm setting lockout is indicated.
•
‘D/P’ and ‘Fnc’ indicators turn on.
NOTE
•
‘AOFF’ or ‘A ON’ is indicated depending on the setting.
•
With no-alarm-output type, the scaling setting lockout ‘SOFF’ or ‘S ON’ is indicated depending on the setting.
1,2,
4,5
2,4,
5
3
3
1