![background image](http://html1.mh-extra.com/html/m-system/47llc/47llc_operating-manual_3126851100.webp)
100
47LLC OPERATING MANUAL EM-9505-B Rev.4
3
Press Shift button to shift the display into the setting standby
mode.
•
The forth digit starts blinking, to which you can apply changes.
4
Press Shift and Up buttons to set the LL (L, H or HH) deadband.
•
Set within the range of 0001 to 9999.
NOTE
•
Setting the deadband to 0000 is available. However it will be changed to 0001 after the power cycle, turned OFF and
ON.
•
Set the deadband for the setpoint. The decimal point is not indicated.
5
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
•
And the next parameter setting is indicated.
NOTE
•
Press Alarm/
↓
button, and the LL (L, H or HH) ON delay time will be indicated within the range of 00 to 99 depending on
the setting.
•
Press Scale/
↑
button, and the LL (L, H or HH) trip action ‘LMLO’ or ‘LMHI’ will be indicated depending on the setting.
6
■
TO GO ON TO SET ANOTHER DEADBANDS,
Repeat operation from Step 2.
■
TO SET THE NExT PARAMETER,
Skip to Step 2 in “11.5 ON DELAY TIME”.
■
TO qUIT,
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.
Blinking