65
47LLC OPERATING MANUAL EM-9505-B Rev.4
3
Press Alarm/
↓
or Scale/
↑
button to go to the load ratio setting.
•
The load ratio is indicated.
•
‘Spn’ and ‘Fnc’ indicators turn on.
NOTE
Skip to Step 7 if the default value is acceptable.
4
Press Shift button to shift the display into the setting standby
mode.
•
The forth digit starts blinking, to which you can apply changes.
5
Press Shift and Up buttons to set to ‘10.0’.
•
Press Shift button to go to the next digit and Up button to change
the blinking value.
NOTE
•
‘10.0’ is a display example. Set any value within the setting range.
•
‘Min’ and ‘Max’ indicators start blinking when the set value is within invalid range. Return the setting within the valid
range.
6
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
•
And the next parameter setting is indicated.
NOTE
•
Press Alarm/
↓
button, and the input scaling value B will be indicated.
•
Press Scale/
↑
button, and the display scaling value A will be indicated within the range of -19999 to 19999 depending
on the setting.
Blinking
Blinking