47LLC OPERATING MANUAL EM-9505-B Rev.4
7.3 TARE ADJUsTMENT VIA EXTERNAL CONTACT INPUT
Procedures to adjust the vessel weight 30.0 kg via external contact input are described here with the display scaling 0.0 –
300.0 kg.
7.3.1 OPERATING PROCEDURE
1
With the contact input OFF (open), put the empty vessel on
the strain gauge.
•
The vessel weight is indicated.
2
Confirm that the indication is stable, and turn ON (close) the
contact input to adjust the tare.
•
The value equivalent to the display scaling value A is indicated.
3
Confirm that the indication is stable, and turn OFF (open) the
contact input.
•
The tare input is registered.
IMPORTANT
•
Turning ON the contact input executes tare adjustment even while in setting other parameters. Turn OFF the contact
input except in adjusting tare.
•
The tare adjustment resets the alarm and DC outputs to 0%, corresponding to the display scaling value A.
•
Even while ‘S.ERR’ is indicated, the tare is adjustable within the valid range. Adjusting beyond the range is not avail-
able. Review the vessel in such a case.
•
Once registered, the tare input is indicated in setting the tare adjustment as voltage equivalent to the vessel
input scaling value A.
*