145
47LLC OPERATING MANUAL EM-9505-B Rev.4
22.3 PARAMETER LIsT
MODE
PARAMETER
SETTING RANGE
INDICATOR
DISPLAY
DEFAULT
VALUE
DECIMAL
POINT
POSITION
UNIT
Measuring Present value
-19999 – 19999
,
,
,
,
----
----
*
1
User-defined
MAX value
-19999 – 19999
----
----
*
1
User-defined
MIN value
-19999 – 19999
----
----
*
1
User-defined
LL alarm setpoint
-19999 – 19999
----
----
*
1
User-defined
L alarm setpoint
-19999 – 19999
----
----
*
1
User-defined
H alarm setpoint
-19999 – 19999
----
----
*
1
User-defined
HH alarm setpoint
-19999 – 19999
----
----
*
1
User-defined
Scaling
setting
Input type
S1: 0.0 – 1.0
,
----
mV/V
S2: 0.0 – 3.0
S3: 0.0 – 10.0
S4: 0.0 – 30.0
Excitation voltage
2.5, 5, 7.5, 10
,
,
,
----
V DC
Input scaling value A
S1: -10.00 – 10.00
,
to
----
mV DC
S2: -30.00 – 30.00
to
S3: -100.0 – 100.0
to
S4: -300.0 – 300.0
to
Display scaling value A
-19999 – 19999
,
to
*
1
User-defined
Load ratio
10.0 – 100.0
,
to
----
%
Input scaling value B
S1: -9.00 – 20.00
,
to
----
mV DC
S2: -27.00 – 60.00
to
S3: -90.0 – 200.0
to
S4: -270.0 – 600.0
to
Display scaling value B
-19999 – 19999
,
to
*
1
User-defined
Tare adjustment
S1: -8.00 – 8.00
,
,
to
----
mV DC
S2: -24.00 – 24.00
to
S3: -80.0 – 80.0
to
S4: -240.0 – 240.0
to
Decimal point position
No decimal point,
or 10
-1
to 10
-4
,
,
,
,
----
----
Analog output function
mode
Proportional to the display
value,
Proportional to the scaling
value
,
----
----
Analog output 0%
adjustment
Adjustable range
-5 to +100%
,
:
(increasing)
(decreasing)
0% output
----
----
Analog output 100%
adjustment
Adjustable range
0 to 105%
,
:
(increasing)
(decreasing)
100%
output
----
----
*
1 Conforms to decimal point position setting.
NOTE 1: Indicators with the present value in Measuring Mode depend on the set alarm trip action.
NOTE 2: INDICATOR:
= ON,
= Blinking
NOTE 3: S1 through S4 in the columns of SETTING RANGE in Scaling Setting Mode show input strain gauge codes.