![background image](http://html1.mh-extra.com/html/m-system/47llc/47llc_operating-manual_3126851134.webp)
134
47LLC OPERATING MANUAL EM-9505-B Rev.4
19.2.2 OPERATING PROCEDURE
1
Hold down Scale/
↑
button for 3 seconds or more to move on to
Scaling Setting Mode.
•
The input type is indicated.
•
‘Zro’ and ‘Spn’ indicators turn on.
IMPORTANT
Warm up the unit for 10 minutes or more before carrying out the Analog Output Adjustment.
2
Press Alarm/
↓
or Scale/
↑
button to go to the analog output 0%
adjustment.
•
The analog output 0% adjustment is indicated.
•
‘Zro’ and ‘Fnc’ indicators turn ON.
NOTE
Skip to Step 5 when the analog output 0% adjustment is not necessary.
3
Press Shift button to switch the signal to increase (indication
‘UP’) or decrease (‘DOWN’).
2,5,
8,9
1,2,
8,9
4,7
3,6
Blinking
Blinking
■
Increasing output
■
Decreasing output