47LLC OPERATING MANUAL EM-9505-B Rev.4
3
Press Shift or Up button to select ‘LMHI’.
4
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
•
And the next parameter setting is indicated.
NOTE
•
Press Alarm/
↓
button, and the LL (L, H or HH) deadband will be indicated within the range of 0001 to 9999 depending
on the setting.
•
Press Scale/
↑
button, and the LL (L, H or HH) alarm setpoint will be indicated within the range of -19999 to 19999 de-
pending on the setting.
5
■
TO GO ON TO SET ANOTHER TRIP ACTIONS,
Repeat operation from Step 2.
■
TO SET THE NExT PARAMETER,
Skip to Step 2 in “11.4 DEADBAND”.
■
TO qUIT,
Hold down Alarm/
↓
or Scale/
↑
button for 1 second or more to return to Measuring Mode.