47LLC OPERATING MANUAL EM-9505-B Rev.4
3
Press Alarm/
↓
or Scale/
↑
button to go to the display scaling
value A setting.
•
The display scaling value A is indicated.
•
‘Zro’ and ‘D/P’ indicators turn on.
NOTE
Skip to Step 7 if the default value is acceptable.
4
Press Shift button to shift the display into the setting standby
mode.
•
The fifth digit starts blinking, to which you can apply changes.
5
Press Shift and Up buttons to set to ‘0000’.
•
Press Shift button to go to the next digit and Up button to change
the blinking value.
NOTE
•
‘0000’ is a display example. Set any value within the range of -19999 to 19999.
•
The decimal point position depends on the decimal point position setting. Disregard the decimal point here.
•
The negative sign (-) must be set to the leftmost digit. For example, set ‘-04.00’ instead of ‘-4.00’.
6
Press Alarm/
↓
or Scale/
↑
button to apply the new setting.
•
And the next parameter setting is indicated.
NOTE
•
Press Alarm/
↓
button, and the load ratio will be indicated within the range of 10.0 to 100.0 depending on the setting.
•
Press Scale/
↑
button, and the input scaling value A will be indicated.