222
8
CO/O
2
Control
8.10.5 CO Control: Start-up O
2
Monitoring Shut-off Limits
It is essential to check and ensure that the burner burns stably in every firing rate range at the
shut-off limit of O
2
monitoring, taking into account all environmental influences.
Factory setting of the shut-off limit of O
2
monitoring with CO control activated = 0.4 vol.%.
NOTICE
If the factory-set shut-off limit at 0.4 Vol.% O
2
is too low for your application, there is an option
to raise this via the CMS Remote Software (FE4 required). The LAMTEC Support department
is available for support queries ([email protected] or +49 (0) 6227 6052-33).
NOTICE
Before the shut-off limit is traversed, the O
2
measurement must be calibrated in accordance
with the specifications in the basic documentation (see chapter
1.1 Validity of these Instruc-
Fig. 8-13 Setting the shut-off limit of O
2
monitoring
P206
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...