235
8
CO/O
2
Control
Behaviour during optimisation
Fig. 8-28 Parameter of the CO controller - behaviour during optimisation
Description of the window ’Parameter of the CO controller - behaviour during optimisa-
tion’
NOTICE
Special situation: P 202 (low fire) > P 203 (high fire). In this case, the CO controller is only
activated outside the parameter set firing rate values.
1
CO controller type
0 = OFF
1 = ON
(default)
2
Smallest permissible O
2
value/tolerance time during monitoring
Smallest permissible O
2
value (1/10 %) until the CO controller is switched off. If the
O
2
value remains below this parameter set limit (P 204) for longer than the time set in
P 205, the CO control switches off.
3
Low fire
Enter the firing rate value at which CO control is activated. The entry is made in digit.
Factory setting: 000
High fire
Enter the firing rate value at which CO control is deactivated. in digit.
Factory setting: 999
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...