31
4
CMS Components
Part number
MCC – Master Control Component
Type 668R1000-XX
*
*
XX = depends on configuration
Function
Supply voltage
MCC
Inputs
Outputs
24 VDC +/
−
20%, SELV
230
V/120 V +10/
−
15%, 47–63
Hz, 24 VDC ±20%
230
V/120 V +10/
−
15%, 47–63
Hz, 24 VDC ±20%
Maximum backup fuse/outputs
8
A
fast-acting
Current draw
Min: 200 mA
Max: 335 mA
Power consumption max.
10 W
Digital inputs
Nominal
current:
2.3 mA (230 VAC), impedance 100 k
Ω
2.1 mA (120 VAC), impedance 100 k
Ω
2.1 mA (24 VDC), impedance 100 k
Ω
Since the inrush currents on the are low, use gold-plated silver
contacts.
Signal ON:
0.78 mA (230 VAC) 77 VAC
0.97 mA (120 VAC) 56 VAC
0.55 mA (24 VDC) 6.9 VDC
Signal OFF:
0.35 mA (230 VAC) 36 VAC
0.35 mA (120 VAC) 21 VAC
0.27 mA (24 VDC) 4 VDC
Digital outputs
I
max
= 2 A per output, but not to exceed 8 A in total
cos
0.2
Residual voltage possible due to self-test function.
Flame sensor input
Optical: Flame sensor connection FFS07 or FFS08
U
nom
= 27 V ±1 V
Ionisation: 230 VAC (120 VAC) supply voltage
I
min
= 1
A
I
max
= 50
A
Cable length max: 300 m, shielded.
Current output
0 - 20 mA ±2%
Output current max: 25 mA
Load max: 1 k
Ω
Use shielded cables only!
Analogue input
Multifunctional input for the connection of:
– Potentiometer (2 k
Ω
… 10 M
Ω
)
– TPS (see wiring diagram chapter)
– Power input 0/4 - 20 mA, Ri = 150
Ω
– Voltage input 0 - 10 V, Ri = 100
M
Ω
Reference voltage 10 V, short-circuit proof
Tolerance ±2%
Use shielded cables only!
Fieldbus
MODBUS TCP
LAMTEC SYSTEM BUS
Other Fieldbus protocols using separate modules
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...