265
9
Faults
No.
Description
D1
D2
Extra
355
Ignition in mixed operation
FAT tries to ignite in a mixing curve
Internal
information
Fuel train
R = 0
Reset
356
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
R = 0
Power ON Reset
357
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
R = 0
Power ON Reset
380
Band failure: Setpoint is outside the expected range
The watchdog processor detects a band failure.
Setpoint or actual value of an actuator is not in the
expected range.
Setpoint minimum
lower 12 bits: set-
point maximum
Channel number
in the bits above
bit 12
R = 0, 0, 0, 0
Reset
381
Actuator dynamics is missing
The ÜP has not detected the required dynamics for
at least one actuator.
Problem:
The actual position of the actuator has not
changed in the last 24 hours.
– Check air damper and gas damper for jamming.
– In case of stiffness, clean the damper and
make it smooth running again.
– Check the function of the actuator without
damper and replace if necessary.
– Reset fault and switch mains voltage OFF
and ON again.
– If the error still exists, replace the device.
0: Actuator
dynamics
1: Correction
channel dynamics
Number of actua-
tor or correction
channel (starting
with 0)
R = 0
Reset
382
Monitoring data from the bus are missing
The watchdog processor requires certain data for
monitoring. These are read at the bus. Currently
required data are missing
Reason:
– Invalid channel configuration
– A non-existing channel is activated
– An inactive channel is marked in the channel
enable mask
1: Actual curve
set
3: Actual value,
channel no. in
P 2
4: Setpoint value,
Channel no. in
P 2
5: Firing rate
value
P 1 = 3 or 4,
Channel no.
(starting at 0)
P 1 = 5,
special fault code
R = 0
Power ON Reset
383
Invalid curve set selection
– Ensure that there is no fuel change during curve
set programming.
– Reset fault
0
0
R = 0
Power ON Reset
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...