86
5
Functional Description with Process Diagrams
5.2.2
Standby Mode
NOTICE
The pilot flame scanner must either be approved for continuous operation or the pilot flame is
monitored together with the main flame with a flame scanner approved for continuous opera-
tion.
NOTICE
For the standby function, please consult both the Installation Manual and Commissioning
Manual, and also take into account the specific requirements for the combustion system.
5.2.2.1 Requirements
Paid option
•
The burner must be equipped with a pilot valve and a pilot flame and must be ignitable by
this valve/flame.
•
The standby operation input must be configured (see chapter
•
The fuel supply for the ignition must not be taken from between the main valves
5.2.2.2 Required Inputs/Outputs
Inputs:
•
Standby operation is active
•
Pilot air pressure monitor (optional)
Outputs:
•
Pilot valve
•
Pilot air fan (optional)
5.2.2.3 Required Parameters
P no.
Description
Attributes
42
Standby mode (0 = OFF, 1 = ON)
V1.0.0.0
Standby mode
0 = OFF
1 = ON
Write: 4
Read: 7
Default: 0
Min.: 0
Max.: 1
808
Pilot air operation (0-OFF; 1-Pilot fan output and pilot fan air pressure signals)
V1.1.0.0
0: Pilot air operation OFF
1: Pilot air operation ON
The pilot air operation requires the pilot fan output and the air pressure signals of the pilot
fan.
Write: 2/GUI/UI
Read: 0
Default: 0
Min: 0
Max:1
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...