16
2
Safety
2.3.2
Installation Notes
•
Always lay the high-voltage ignition conductor separately and as far away as possible from
the device and the other conductors.
•
Observe the relevant local and national regulations when wiring the electrical cables within
the burner.
•
Tighten the screw terminals using a tightening torque >0.5Nm.
•
Supply the feed cable with L, N and PE only. The N neutral conductor must not have po-
tential difference to the PE protective conductor.
•
The pre-fuse on CMS is permitted to be max. 8
A fast-acting per output module (MCC and
output module).
•
Ensure that strain relief of the connected conductors complies with relevant standards
(e.g. DIN EN 60730 and DIN EN 60 335).
•
Ensure that no spliced strands can come into contact with any of the adjacent connec-
tions. Use suitable end splices.
•
To replace or disconnect the plug-in connectors, all poles of the plant must be disconnect-
ed from the mains.
•
The connection between the actuating drives and actuator devices for the fuel and com-
bustion air, as well as to any additional actuator devices that may be in use, must be pos-
itive locking.
•
When wiring components with protective extra low voltage (SELV), and in connected de-
vices, make sure there is a safe separation to the mains voltage.
•
Only connect passive or non-interacting devices to the CMS firing rate outputs (e.g. relay
without additional power supply). In the event of a fault, a supply of 230 V must be exclud-
ed to the CMS via these terminals.
•
Use gold-plated silver contacts on 24 VDC inputs.
•
To avoid faults on the LSB, the termination via P 1010 must be switched to active on the
first and last device connected to the bus.
•
Via installation of the CMS modules, the flame sensor and all additional equipment, the
minimum protection class IP40 – or IP54 for use outdoors – must be ensured in accord-
ance with EN 60529.
•
The analogue inputs connected to the modules must have the same potential as the pow-
er supply of the CMS system.
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...