Faults
No.
Description
D1
D2
Extra
401
Fallen below the smallest, permissible O
2
value
The O
2
trim does not work on this burner.
– Check the electronic ratio control curve
O
2
actual value in
0,1 % O
2
23;1
R = 0, 0, 0, 0
Reset
402 - 425 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
426
Exceeding the maximum, valid CO probe voltage
Probe voltage (in mV with an 1
V)
Probe
voltage
(mV with an off-
set of +1
V)
0
R = 0
Reset
427
Exceeding the maximum, valid CO actual value
0
0
R = 0
Reset
428 - 457 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
458
Exceeding the parameter set U
CO
-MAX-value
The main processor has not detected that the maxi-
mum permissible CO probe voltage has been
exceeded.
Probe voltage
(in mV with an off-
set of +1 V)
0
R = 0
Reset
459
Exceeding the parameter set CO
e
-MAX-value
The main processor has not detected that the maxi-
mum permissible CO actual value has been
exceeded
CO actual value in
ppm
0
R = 0
Reset
461
Exceeding the parameter set O
2
-MIN-value
The main processor has not detected that the mini-
mum permissible O
2
value has been exceeded
O
2
actual value
in 0,1 % O
2
0
R = 0
Reset
470 - 820 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...