217
8
CO/O
2
Control
NOTICE
See safety concept in chapter
6. Set response threshold of the CO detection on the LT3-F.
8.10.7 Set and Optimise the CO Response Threshold on LT3-F
7. Put CO control into operation.
8.10.8.1 Commissioning with UI400
.
8.10.8.2 Operating with PC Remote Software
.
8. Set control parameters and dead time of the O
2
trim on CMS.
Setting the 'Proportional Factor' and 'Dead Time' Control Parameters
Setting the 'Proportional Factor' and 'Dead Time' Control Parameters
9. Check settings on CMS and LT.
Exiting SETTING Mode
– via CMS Remote Software
10. Back up dataset from CMS and LT3-F using CMS Remote Software (download).
Information on this is included in the basic documentation (publication no. DLT3140)
The commissioning of CO/O
2
control is now complete.
8.10.2 Putting the Electronic Ratio Control System into Operation
Commissioning of the electronic ratio control system and O
2
measurement, as described in
the device-specific instructions referred to in Chapter
1.1 Validity of these Instructions
.
The integrated CO/O
2
control remains deactivated.
7 Operating Control and Displays
P 200 = 0
CO control is deactivated.
P 200 = 1
Standard (O
2
= OIL/CO = Gas)
(see chapter
8.10.8.2 Operating with PC Remote Software
WARNING!
An incorrect setting can result in explosion.
This can result in severe injuries or death.
Note the burner manufacturer's instructions with regard to settings.
The burner (basic setting without O
2
trim or CO control) must be set so that it burns stably
under all operating conditions and the emission limit values are observed. For the ’Deactivated
CO/O
2
control’ operating condition, a correct offset for inactive control with excess air must be
set (at the factory).
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...