5
Functional Description with Process Diagrams
NOTICE
This function is active only from software version 2.0.
Process Diagram 'Purging after Operation'
Fig. 5-12 Process sequence chart for purging oil gun
t5
is the waiting time until the actuators have reached the purging position. The purging valve
is then opened.
t5 + t3
produce the purging duration (total). During the entire process, the safety interlock
chain oil must be secured.
NOTICE
If the purging valve is activated by P 812 = 1 and after closing the oil valve, without having
waited for t2, t5 first and not having reached the required position, the flame will not be mon-
itored during the time t2.
7
Control
t6
Transformer pre-activation time P309 0.0 s - 40.0 s
8
Burner OFF
t13
Post-ventilation time P 319 0.0 s - 999 s
t19
Duration of purging P 810 0.0 s - 999.9 s
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...