254
9
Faults
No.
Description
D1
D2
Extra
119
Analogue input: Invalid measurement value of the
reference voltage
The measured values of the reference voltage out-
puts of the fail-safe analogue inputs do not match on
the main processor and watchdog processor.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Input number
Own reference
R = 0
Reset
120 - 183 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
184
Too many signals at one terminal
Several logical signals are mapped to one physical
terminal.
– Check the I/O configuration.
Logic signal
HI Byte: ModuleID
LO Byte: Terminal
R = 0
Power ON Reset
185
An invalid logical signal is pending at the module.
The signal type does not match the configuration of
the module
– Check the I/O configuration.
Logical signal
HI Byte: ModuleID
LO Byte: Terminal
R = 0
Power ON Reset
186 - 200 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
201
Parasitic light fault
– Check parasitic light detection (outside door)
– Check flame sensor
– Check positioning of the flame sensor
– Check flame sensor cable for short circuits/broken
wire
– Check grounding of sensor cable
– Check spark igniter and pilot burner
– Check parameter 800 (FE1)
– Check fuel supply
– Check wiring
Internal
information
0
R = 0, 0, 0, 0
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...