280
12
Appendix
12.3
Circuit Diagrams
NOTICE
in progress
12.4
Accessories
12.4.1 Power Supplies
Measurement of the combustion process characteristics:
This must be documented by measuring the characteristic values for an operation
of the furnace at the shut off limits of the ratio control, as well as the set limits of
the correction circuits (e.g. an O
2
.
The combustion is safe at maximum correctional intervention.
The tolerance time for a deviation between the setpoint and actual value of an
actuator greater than B-Band has been set to 3 s by default for the electronic ratio
control (see prEN12067:2012).
Each actuator is then checked that it does not cause any dangerous process con-
dition at its max. speed within 3 s.
Safe burner operation is checked taking into account of the system tolerances
(notes in prEN 12067-2-2012 Annex CC).
Combustion values (exhaust gas measurement) have been checked and cor-
rected where necessary
*
If any servo motors not mentioned in the test report are used, an assessment of the input of the alternative servo motors shall
be available.
Test description
Date/Tester
Result
/
Power Supply
Description
Type
PSU2415 Power supply 100 ... 240 VAC/24 VDC, 15 W
668R0105
PSU2430 Power supply 100 ... 240 VAC/24 VDC, 30 W
668R0030
PSU2460 Power supply 100 ... 240 VAC/24 VDC, 60 W
668R0060
PSU24150 Power supply 100...240VAC/24VDC, 150 W
668R0150
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...