262
9
Faults
No.
Description
D1
D2
Extra
250
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
0
WA = 0
Power ON Reset
251
Invalid feedback of the purge valve
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
Fuel train
R = 0, 0, 0, 0
Reset
252
Valve leakage test: Unknown control line
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Valve leakage test
control line
Code position
R = 0, 0, 0, 0
253
Invalid feedback of the atomiser valve
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
Information
0
R = 0, 0, 0, 0
254
Fuel pressure is too high
The maximum fuel pressure has been exceeded
When burning fuel is oil:
– Check availability of the fuel
– Check oil filter
– Check oil pressure switch
– Check oil pressure
When burning fuel is gas;
– Check availability of the fuel
– Check oil controller when using fuel gas:
– Check gas pressure
– Check gas pressure switch
Internal
information
Fuel train
R = 0, 0, 0, 0
Reset
255
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Internal
information
Fuel train
R = 0
Reset
256
Invalid operating mode
Fault in an internal self-test.
MP and WD recognise the digital input signals at
slightly different times. This may cause an incorrect
change of operating modes.
– Check signal sequence.
– Reset fault and if necessary switch mains OFF and
ON again.
Internal
information
Fuel train
R = 0
Reset
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...