46
4
CMS Components
NOTICE
The limits of the technical data must be strictly adhered to.
Digital output
Non-safe, digital output
Relay output, floating
Voltage up to 230 VAC/50 Hz
Rated current: 2 A, cos
= 0.2
Fuse protec-
tion:
Resettable/electronic 4.1 A max. (voltage-dependent)
Not resettable 5 A fast-acting
Electrically safe separation from SELV power supply voltage of the
CMS system
Outputs
Environmental conditions
Operation
Climatic condition
Class 3K5 as per DIN EN 60721-3-3, 5% ... 95 %
Mechanical condition
Class 3M5 as per DIN EN 60721-3-3
Temperature range
-30...+70
°C (no condensation permitted)
Transport
Climatic condition
Class 2K4 as per DIN EN 60721-3-2,
95 %
Mechanical condition
Class 2M2 as per DIN EN 60721-3-2
Temperature range
-40...+80
°C (no condensation permitted)
Storage
Climatic condition
Class 1K3 as per DIN EN 60721-3-1, 5% ... 95 %
Mechanical condition
Class 1M2 as per DIN EN 60721-3-1
Temperature range
-40...+80
°C (no condensation permitted)
Electrical safety
Protection class according to DIN EN
60529
IP20 (when all terminals are fitted)
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...