255
9
Faults
No.
Description
D1
D2
Extra
202
Flame fault during ignition process
Flame is lost during ignition process.
The fault is caused by invalid ignition settings.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check stability of the fuel pressure
– Check grounding of sensor cable
– Check flame sensor cable for short circuits/
broken wire
– Check wiring
– Check parameter 302, 303 and 800
Internal
information
Fuel train
R = 3, 3, 3, 3
Reset
203
Flame fault during operation
– Check curve settings
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check stability of the fuel pressure
– Check grounding of sensor cable
– Check flame sensor cable for short circuits/
broken wire
– Check wiring
– Check parameter 800
Internal
information
R = 1, 1, 1, 1
Reset
204
Invalid configuration
Cold check cannot be deactivated.
R = 0, 0, 0, 0
Reset
205
Not permitted fuel changeover while burner is operating.
A fuel change was requested although a change via
OFF is
not
configured (P807, FE4).
0
0
R = 0, 0, 0, 0
Reset
208
Remote shut-down was triggered.
The Remote shut-down can be triggered by:
Press the BACK button for too long.
Press the ENTER and BACK button simultaneously.
Disconnect the CMS Remote Software in SETTING
mode (after a waiting time of 45 s)
Clicking the icon
in the CMS Remote Soft-
ware
– Switch off the burner and restart.
0
0
R = 0
Reset
209
Program monitoring times
The Program monitoring time exceeded (P304, FE0)
(FAT).
0
0
R = 0, 0, 0, 0
Reset
210
Invalid CPI signal
Internal
information
Fuel train
R = 0, 0, 0, 0
Reset
211
Ignition position acknowledgement is dropping
The signal ’Ignition position acknowledgement’ is
dropping
Internal
information
Fuel train
R = 1, 1, 1, 1
Reset
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...