87
5
Functional Description with Process Diagrams
5.2.2.4 Functional Description
Fig. 5-9 Process sequence chart for standby operation with the example of gas
Signal bar
Significant times and their parameters
Standard
Signal must be present.
t2
Filling time of the gas path
P313
2.0 s
Signal must not be present.
t9
2nd safety time
P308
3.0 s
Signal can be present.
t11
Control release delay time
P380
0.0 s
t12
Block and bleed of the gas line
P334
3.0 s
t23
Irrelevance time
P323
2.0 s