264
9
Faults
No.
Description
D1
D2
Extra
288
Required dynamics for at least one actuator is miss-
ing
The actual position of the actuator has not changed
for more than 24 h.
– Check air damper and gas damper for
jamming
– Replace the affected actuator
0 = Actuator’s
dynamics
1 = Correction
channel’s
dynamics
Channel number
for actuator or
correction
(starting at 0)
WA = 9
Reset
289
Invalid curve ID of the actual curve set
Reason:
– Wrong curve set loaded
– EEPROM defect
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to
the technical support.
– Replace the device
Curve set
0
R = 0
Power ON
Reset
290
Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
291
Invalid configuration
Incorrect parameter setting
Code position
Value
R = 0, 0, 0, 0
Reset
300 - 313 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
314
Duration of ambient light monitoring was not met [s]
Duration (5 s) of the ambient light monitoring was not
met. The fault may occur during an internal self-test
.– Reset fault and switch mains OFF and ON if
necessary
– If the fault still exists replace the device.
measured time in
steps of 20 ms
0
R = 0
Power ON Reset
315 - 347 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
348
Ignition air is missing
Internal
information
0
R = 0
Power ON Reset
349 - 354 Internal fault
0
0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
Summary of Contents for AEC-TPS
Page 2: ......
Page 131: ...130 7 Operating Control and Displays 7 1 5 5 Deleting Curves Delete firing rate curve...
Page 148: ...147 7 Operating Control and Displays Channel configuration AL1 Fig 7 18 Channel configuration...
Page 157: ...156 7 Operating Control and Displays Fig 7 27 System CRCs menu...
Page 162: ...161 7 Operating Control and Displays Fig 7 32 IP setting menu...
Page 166: ...165 7 Operating Control and Displays Fig 7 35 Installation...
Page 167: ...166 7 Operating Control and Displays Fig 7 36 Installation...
Page 176: ...175 7 Operating Control and Displays Fig 7 49 Loading a protected dataset into the device...
Page 202: ...201 7 Operating Control and Displays Replacing a Module Fig 7 81 Module replacement menu...
Page 276: ...275 10 Maintenance 3 Restart CMS to complete the update...
Page 282: ...281 12 Appendix 12 5 EU Declaration of Conformity...
Page 283: ...282 12 Appendix...